4 FAQs about Zhongneng generator inlet and outlet air temperature diagram

How does a canopy design affect a generator's rated power output?

he canopy design has to allow the correct amount of air in and out. While a generator's rated power output will be reduced as the ambient air temperature increases above 21°C (70°F), the s our calculated to permit air flow requirements for:3.1 RADIATOR:Internal Combustion Engine (ICE) are fited

Should a generator air inlet be facing the wind?

When ever possible, face the generator air inlet openings away from the wind. The wind can prevent the air intake louver from opening on start up. The air inlet must be capable of moving enough air through the room to provide the correct minimum CFM (cubic feet per minute) cooling for generator as specified by the generator's manufacturer.

What is a restriction to air flow in an air cooled generator?

Louvers, screening, expanded metal and other materials used to cover air openings are a restriction to air flow. This restriction must be compensated for by making the air opening size proportionally larger. When possible, position the engine end of air cooled generators in line with the air inlet per the manufacturer's recommendation.

How do you find the size of a generator air duct?

Find the area of the generator's inlet air duct, by multiplying the air duct height by its width. Divide the inlet air duct area by the percentage of free air inlet area for the particular screening or expanded metal to be used. The result is the required size of the air inlet opening in the building.